Radon and its decay products in an air-conditioned auditorium in correlation with indoor air parameters
Artykuł w czasopiśmie
MNiSW
20
Lista A
| Status: | |
| Autorzy: | Połednik Bernard, Kozak Krzysztof, Mazur Jadwiga, Dudzińska Marzenna, Grządziel Dominik |
| Rok wydania: | 2016 |
| Wersja dokumentu: | Elektroniczna |
| Język: | angielski |
| Numer czasopisma: | 5 |
| Wolumen/Tom: | 26 |
| Strony: | 621 - 630 |
| Impact Factor: | 1,181 |
| Web of Science® Times Cited: | 3 |
| Scopus® Cytowania: | 3 |
| Bazy: | Web of Science | Scopus | Web of Science Core Collection |
| Efekt badań statutowych | NIE |
| Materiał konferencyjny: | NIE |
| Publikacja OA: | TAK |
| Licencja: | |
| Sposób udostępnienia: | Otwarte czasopismo |
| Wersja tekstu: | Ostateczna wersja opublikowana |
| Czas opublikowania: | W momencie opublikowania |
| Abstrakty: | angielski |
| The measurements of radon and its attached decay product activity concentrations were carried out in an occupied and unoccupied auditorium during three air-conditioning modes i.e. air-conditioning system switched off (air-conditioning off), air-conditioning system switched off during the night and switched on during the day (air-conditioning on/off) and air-conditioning system switched on (air-conditioning on). Higher average concentrations of radon and its decay products were recorded in the auditorium when the air-conditioning system was switched off. The average particle mass and CO2 concentrations and indoor air thermal parameters were elevated during the air-conditioning on/off mode. A statistically significant (p < 0.001) positive correlation between the decay product concentrations and the particle number and average particle mass concentrations has been observed in the air-conditioning off mode (r = 0.55 and r = 0.68) and in the air-conditioning on/off mode (r = 0.54 and r = 0.62, respectively). A significant negative correlation has been observed between the decay product concentrations and the indoor air temperature and CO2 concentrations in the air-conditioning off mode (r = −0.86 and r = −0.47, respectively). The obtained results confirmed the impact of the air-conditioning system operation on the decrease of health risks related to the presence of radon and its decay products in air conditioned premises. |