Thermal conditions and perceived air quality in an air-conditioned auditorium
Fragment książki (Materiały konferencyjne)
MNiSW
15
WOS
Status: | |
Autorzy: | Połednik Bernard, Guz Łukasz, Skwarczyński Mariusz, Dudzińska Marzenna |
Wersja dokumentu: | Drukowana | Elektroniczna |
Arkusze wydawnicze: | 0.5 |
Język: | angielski |
Web of Science® Times Cited: | 2 |
Scopus® Cytowania: | 2 |
Bazy: | Web of Science | Scopus | Web of Science Core Collection | AIP |
Efekt badań statutowych | NIE |
Materiał konferencyjny: | TAK |
Nazwa konferencji: | 21st International Meeting on Thermophysics |
Termin konferencji: | 12 września 2016 do 14 września 2016 |
Miasto konferencji: | Terchova |
Państwo konferencji: | SŁOWACJA |
Publikacja OA: | NIE |
Abstrakty: | angielski |
The study reports measurements of indoor air temperature (T) and relative humidity (RH), perceived air quality (PAQ) and CO2, fine aerosol particle number (PN) and mass (PM1) concentrations in an air conditioned auditorium. The measurements of these air physical parameters have been carried out in the unoccupied auditorium with the air conditioning system switched off (AC off mode) and in the unoccupied and occupied auditorium with the air conditioning system switched off during the night and switched on during the day (AC on/off mode). The average indoor air thermal parameters, CO2 concentration and the PAQ value (in decipols) were elevated, while average PM1 concentration was lower in the AC on/off mode. A statistically significant (p < 0.001) positive correlation has been observed between T and PAQ values and CO2 concentrations (r = 0.66 and r = 0.59, respectively) in that AC mode. A significant negative correlation has been observed between T and PN and PM1 concentrations (r = −0.38 and r = −0.49, respectively). In the AC off mode the above relations between T and the particle concentrations were not that unequivocal. These findings may be of importance as they indicate that in certain AC operation modes the indoor air quality deteriorates along with the variation of the indoor air microclimate and room occupation. This, in turn, may adversely affect the comfort and productivity of the users of air conditioned premises. |